Menu
Back

HygroFlex3 - HF3 - HVAC transmitter

R-Type / S-Type
Measures relative humidity and temperature and calculates the dew/frost point in offices and rooms where good looks play a role.

W-Type / D-Type
Measures relative humidity and temperature and calculates the dew/frost point in HVAC applications focused on relability and repeatability.

Features

• Accuracy: ±2 %rh / ±0.3 K at 23°C ±5 K
• Temperature limit at probe: -40…60 °C / 0…100 %rh
• Range of application electronics: -40…60 °C / 0…100 %rh, -10…60 °C with LCD
• Service interface
• Adjusted at 23 °C and 10, 35, 80 %rh

Probe type Integrated
Operating range -40…60 °C / -10…60 °C (Models with display) 0…100 %rh, non-condensing
Accuracy at 23 ±5 °C ±2.0 %rh / ±1.0 %rh (Type R), ±0.3 K / ±0.2 K (Type R)
Measuring range with integrated probe -40…60 °C / 0…100 %rh
Power supply / Power consumption 15…40 VDC or 12…28 VAC/ <100 mA
Probe protection Polycarbonate plastic cage, white
Filter cartridge Polyethylene dust filter, gray, 20 um
Response time t 63 <12 s for 63% of a 35> 80% (1 m / sec air flow at the sensor)
Allowed wind speed 20 m/s, with filter
Psychrometric calculations Dew or frost point
Reproducibility Airchip <0.02 %rh / 0.01 K
Measurement interval typically 1 second (without calculations)
Display type Optional graphics display. Presentation configurable.
Backlight with Backlight
Alarm indicators Yes
Exploitation software ROTRONIC HW4
Trend indicator Yes, for models with display
Probe adjustment by software Yes, with service cable
Remote control functions Via HygroPalm and service cable
Firmware update With internet and HW4 software
User information from Software HW4 (devicemanager)
Data processing via HW4 with interface cables
Device Protection by password Yes
Type of output signals 2
Analogue outputs scaleable by the user Yes
Change of output signal w/o adjustment Yes
Analog output signal (standard) 0…20 mA, 4… 20 mA; 0… 1 V, 0… 5 V, 0… 10 V
Digital output signal (standard) UART
Min. / max. load voltage / current signal V min = 10 V + (0.02 x Load*) * = Resistance in ohms
Service Interface Mini USB (UART)
Service Information Calibration interval
Max. cable length Up to 5 m with passive cable. Up to 100 m with active cable.
Probe material Polycarbonate
Enclosure material ABS
IP protection rating HF3x-S/ HF3x-R: IP20
HF3x-W/ HF3x-D: IP65
Fire protection class Complies UL94-HB
FDA/GAMP compatibility FDA 21 CFR Part 11 and GAMP compatible
Dimensions Wall: ø 82 x 43, probe length 100 mm
Duct: ø 82 x 43, probe length 207 mm
Room: 82 x 82 x 26 mm

Want to learn more about our products?
We will be pleased to personally advise you.

+41 44 838 11 44
measure@rotronic.ch

Contact Information

* Required Fields