Back
RMS-DO-L-R - Digital Output Module
The digital output module serves to display information, issue alarms and control events. The relays can be interrogated or set via Modbus TCP or the RMS software. It is possible to define the conditions in the RMS software and to actuate the outputs on the basis of them.
Advantages
- Two output channels
- Compatible with RMS-Config, RMS On-Premise and RMS SaaS
- Conforms to FDA CFR 21 Part 11 / GAMP 5
Applications
- Monitoring / Process control
- Building automation
- Industrial automation
Compatible with:
- RMS-Config
- RMS-WEB On-Premise
- RMS-CLD SaaS solutions
Device type | RMS-DO-L-R |
---|---|
Number of outputs | 2, polarity-independent |
Range of application | -40…70 °C / 0...100 %RH |
Power consumption | 24 VDC ±10 % / <100 mA / PoE: 802.3af-2003, Class 1 |
AC adapter requirements | 24 VDC ±10 % / 4 W nominal /<15 W power-limited |
Interface | Digital signal / galvanically isolated |
Relay switching capacity | 50 VAC (peak) 1 A / 50 VDC/1 A, polarityindependent |
Measurement interval | >=10 s |
Communication interfaces | Ethernet |
Protocols | HTTP |
Fire protection class | UL94-V0 |
Housing | Polycarbonate |
IP protection rating | IP20 |
Max. cable length | <3 m |
FDA / GAMP | FDA 21 CFR part 11 / GAMP5 |
Storage and transport conditions | -40..30 °C / 0..95 %RH |
Dimensions | 89.7 x 62.2 x 108 mm |
Maximum altitude | 2000 m ASL |
Weight | 155 g |
Want to learn more about our products?
We will be pleased to personally advise you.