CO2 – Measurement and Monitoring of Carbon Dioxide in Rooms

CO2 Display

The wall-mounted or bench-top CO2 display is the latest development of an inexpensive display unit that simultaneously measures and records CO2, humidity and temperature. Equipped with the field-tested ROTRONIC HYGROMER® IN-1 humidity sensor, this instrument offers unbeatable value for money. The instrument can be configured directly with buttons and stored data can be exported to a USB stick for analysis with the free ROTRONIC software package SW21.

Guidelines for a healthy indoor climate (CO2, %rH and °C)

The monitoring of important indoor air parameters helps to minimize the risk of infection with viruses or bacteria and to increase well-being and concentration.
Download our free poster here

CO2 measurement - Measuring carbon dioxide in rooms - Recommendations - Information

Applications
Indoor Air Quality: Classrooms, Meeting Rooms, Open-Plan Offices, Shopping Centers, Fitness Studios...

Features
• Measures and records CO2, relative humidity and temperature
• Accuracy ±2.5 %RH / ±0.3 K / ±30 ppm + 5% of measured value
• ROTRONIC HYGROMER® IN-1 humidity sensor
• 18,000 data point memory for CO2, humidity and temperature values
• Display of date and time
• Adjustable, visual CO2 indicator
• Large, easy-to-read display
• USB access for data download

More Information
Humidity sensor ROTRONIC HYGROMER® IN-1
Temperature sensor NTC
Long-term stability < 1.5 %RH per year
Measuring range 0…5000 ppm / 0...100 %RH / -20...60 °C
Accuracy at 23 ±5 °C ±30 ppm ±5 % of the measured value, <2.5 %RH (10...90 %RH), ±0.3 °K
Response time t 63 <30 s, without filter
Power consumption AC adapter 12 VDC
Dimensions 330 x 250 x 50 mm
Alarm indicators Adjustable for CO2 measurement
Memory size 18,000 values with time stamp, automatic recording (%RH / °C / ppm)
Weight 1400 g
Housing ABS
Parameters shown CO2, relative humidity and temperature
Clock Real time clock
Current consumption 700 mA (max)
CE / EMC conform 2004/108/EC
Measurement principle Infrared (NDIR) with automatic calibration (ABC)
Response time CO2 : <3 min. diffusion time / T°: 4s
Adjustment points 0, 400 ppm and 35, 80 %RH
Pressure dependence +1.6 % reading per kPa
Zero drift <10 ppm/year
Maintenance No maintenance (standard indoor application)
Warm-up time <1 min.