The digital input module stores all measured data on an event basis and sends it to the database via Ethernet. The minimum pulse time is 100 ms. Should the connection be lost, the module stores the data intermediately to protect data integrity and fills up the data gaps when the connection has been restored. The device has a battery so that logging of measured data is also ensured in the event of a failure in the external power supply.

Advantages

  • Two input channels
  • Data logging of up to 75,000 measured values
  • Compatible with RMS-Config, RMS On-Premise and RMS SaaS
  • Conforms to FDA CFR 21 Part 11 / GAMP 5

Applications

  • Monitoring / Process control
  • Safety and automation
  • Direct condition control

Compatible with:

  • RMS-Config
  • RMS-WEB On-Premise
  • RMS-CLD SaaS solutions
More Information
電源 / 消費電力 >24 VDC ±10 % / <100 mA / PoE: 802.3af-2003, Class 1
寸法・サイズ 89.7 x 62.2 x 108 mm
IP保護等級 IP20
耐火クラス UL94-V0
測定間隔 Event-based & interval (10 s to 15 min.)
通信インターフェース Ethernet
ケーブル最大長 <3 m
重量 206 g
ハウジング材質 Polycarbonate
FDA / GAMPへの対応 FDA 21 CFR part 11 / GAMP5
バッテリ寿命 3 years at 23 °C
入力 2 independent digital inputs
デバイス種類 RMS-DI-L-R
保管および輸送条件 -40..30 °C / 0..95 %RH
電池 RMS-BAT
記憶容量 75,000 data points
Maximum altitude 2000 m ASL
AC adapter requirements 24 VDC ±10 % / 4 W nominal /<15 W power-limited
Input frequency Max. 0.833 Hz or 1.2 s
Pulse recognition >100 ms (periodically > 1.2 s)
Input circuit Logic level: 0 V / 5-24 V
Trigger threshold: ~3.77 V
Current consumption: <1 mA
Reed circuit Max. load at input 100 kΩ